H7 ADC3的温度传感器采集值转换后温度总是120多度

本帖最后由 fendoushuai 于 2024-3-28 18:10 编辑

从H7的ADC3 19通道读取的温度值转换后总是120多度
是需要对它进行校准吗?还是有别的配置

printf打印的结果如下

TS_CAL1=12220, TS_CAL2=16301
ADC3_INP19 TEMP Value=17179, Voltage= 127.211 C,


static void AppTaskADC(void *p_arg)
{
    float AdcValues;
    uint16_t TS_CAL1;
    uint16_t TS_CAL2;

    (void)p_arg;

    while(1) {
      BSP_vToggleLED(LED_YELLOW);

      TS_CAL1 = *(__IO uint16_t *)(0x1FF1E820);
      TS_CAL2 = *(__IO uint16_t *)(0x1FF1E840);   
      AdcValues = (110.0 - 30.0) * ( aADC3ConvertedData - TS_CAL1) / (TS_CAL2 - TS_CAL1) + 30;

      printf("TS_CAL1=%d, TS_CAL2=%d\r\n", TS_CAL1, TS_CAL2);
      printf("ADC3_INP19 TEMP Value=%d, Voltage= %5.3f C,\r\n", aADC3ConvertedData, AdcValues);

      OSTimeDlyHMSM(0, 0, 2, 0);
    }
}


/* ### - 1 - Initialize ADC peripheral #################################### */
hadc3.Instance          = ADC3;
if (HAL_ADC_DeInit(&hadc3) != HAL_OK) {
    /* ADC de-initialization Error */
    Error_Handler(__FILE__, __LINE__);
}

hadc3.Init.ClockPrescaler         = ADC_CLOCK_ASYNC_DIV1;            /* Asynchronous clock mode, input ADC clock divided by 1*/
hadc3.Init.Resolution               = ADC_RESOLUTION_16B;            /* 16-bit resolution for converted data */
hadc3.Init.ScanConvMode             = DISABLE;                         /* Sequencer disabled (ADC conversion on only 1 channel: channel set on rank 1) */
hadc3.Init.EOCSelection             = ADC_EOC_SINGLE_CONV;             /* EOC flag picked-up to indicate conversion end */
hadc3.Init.LowPowerAutoWait         = DISABLE;                         /* Auto-delayed conversion feature disabled */
hadc3.Init.ContinuousConvMode       = ENABLE;                        /* Continuous mode enabled (automatic conversion restart after each conversion) */
hadc3.Init.NbrOfConversion          = 1;                               /* Parameter discarded because sequencer is disabled */
hadc3.Init.DiscontinuousConvMode    = DISABLE;                         /* Parameter discarded because sequencer is disabled */
hadc3.Init.NbrOfDiscConversion      = 1;                               /* Parameter discarded because sequencer is disabled */
hadc3.Init.ExternalTrigConv         = ADC_SOFTWARE_START;            /* Software start to trig the 1st conversion manually, without external event */
hadc3.Init.ExternalTrigConvEdge   = ADC_EXTERNALTRIGCONVEDGE_NONE;   /* Parameter discarded because software trigger chosen */
hadc3.Init.ConversionDataManagement = ADC_CONVERSIONDATA_DMA_CIRCULAR; /* ADC DMA circular requested */
hadc3.Init.Overrun                  = ADC_OVR_DATA_OVERWRITTEN;      /* DR register is overwritten with the last conversion result in case of overrun */
hadc3.Init.OversamplingMode         = DISABLE;                         /* No oversampling */

/* Initialize ADC peripheral according to the passed parameters */
if (HAL_ADC_Init(&hadc3) != HAL_OK) {
    Error_Handler(__FILE__, __LINE__);
}
   
/* ### - 2 - Start calibration ############################################ */
if (HAL_ADCEx_Calibration_Start(&hadc3, ADC_CALIB_OFFSET_LINEARITY, ADC_SINGLE_ENDED) != HAL_OK) {
    Error_Handler(__FILE__, __LINE__);
}


      /* ### - 3 - Channel configuration ######################################## */
sConfig.Channel      = ADC_CHANNEL_TEMPSENSOR;                /* Sampled channel number */
sConfig.Rank         = ADC_REGULAR_RANK_1;          /* Rank of sampled channel number ADCx_CHANNEL */
sConfig.SamplingTime = ADC_SAMPLETIME_810CYCLES_5;   /* Sampling time (number of clock cycles unit) */
sConfig.SingleDiff   = ADC_SINGLE_ENDED;            /* Single-ended input channel */
sConfig.OffsetNumber = ADC_OFFSET_NONE;             /* No offset subtraction */
sConfig.Offset = 0;                                 /* Parameter discarded because offset correction is disabled */
if (HAL_ADC_ConfigChannel(&hadc3, &sConfig) != HAL_OK) {
    Error_Handler(__FILE__, __LINE__);
}



滴滴滴 发表于 2024-3-29 09:06:03

注意基准电压的范围,官方给的公式的基准电压和你的基准电压是否一致?如果不一致要改变公式的!我之前测试温度一直是120度,怎么也查不到问题,后面是发现是基准电压问题

eric2013 发表于 2024-3-29 09:15:08

1、注意你的稳压基准,我们之前做的那个例子是3.3V稳压下测量的。
2、使用ADC功能,板子最好是外置电源供电。

fendoushuai 发表于 2024-3-29 10:09:00

板子电压参考电压是2.5V,调整了计算公式,使用HAL库中的函数__HAL_ADC_CALC_TEMPERATURE_TYP_PARAMS可以得到温度了

eric2013 发表于 2024-3-30 08:40:57

fendoushuai 发表于 2024-3-29 10:09
板子电压参考电压是2.5V,调整了计算公式,使用HAL库中的函数__HAL_ADC_CALC_TEMPERATURE_TYP_PARAMS可以得 ...

那确实方便了。